Temperature Drift | +/- 0.02 %/°C of the maximum setting value IEC 61812-1 | Humidity Drift | +/- 0.05 %/%RH of the maximum setting value IEC 61812-1 |
Repeat Accuracy | +/- 0.2 % of the maximum setting value IEC 61812-1 | Voltage Drift | +/- 0.2 %/V of the maximum setting value 48...240 V || +/- 1 %/V of the maximum setting value 24...4 |
Setting Accuracy Of Time Delay | +/- 5 % of full scale 25 °C IEC 61812-1 | Operating Temperature | -4…122 °F (-20…50 °C) |
Ambient Air Temp For Storage | -40…158 °F (-40…70 °C) | Product Weight | 0.31 lb(US) (0.14 kg) |
Vibration Resistance | 0.35 mm (f= 10…55 Hz) conforming to IEC 60068-2-6 | Time Delay Range | 0.5...30 s || 5...300 s || 0.2...12 min || 0.5...30 h || 2...120 s || 0.05...3 s || 0.2...12 s || 0. |
Power Consumption In W | 0.5 W 24 V || 1.7 W 240 V | Voltage Range | 0.85...1.1 Us AC || 0.9...1.1 Us DC |
Power Consumption In Va | 1.1 VA 24 V || 4.8 VA 240 V | Dielectric Strength | 1 kV 1 mA/1 minute IEC 61812-1 |
Surge Withstand | 1 kV differential mode IEC 61000-4-5 level 3 || 2 kV common mode IEC 61000-4-5 level 3 | Immunity To Microbreaks | 10 ms |
Imm To Radioelectric Fields | 10 V 0.15...80 MHz)EN/IEC 61000-4-6 level 3 | On-load Factor | 100 % |
Minimum Switching Current | 100 mA | Electrical Durability | 100000 cycles |
Breaking Capacity | 1250 VA | Warranty | 18 months |
Contacts Type And Composition | 2 C/O timed contacts, AgNi (cadmium free) | Resistance To Fast Transients | 2 kV EN/IEC 61000-4-4 level 4 capacitive connecting clip) || 4 kV EN/IEC 61000-4-4 level 4 direct) |
Minimum Pulse Duration | 20 ms | [us] Rated Supply Voltage3 | 24...240 V AC/DC 50/60 Hz |
Output Voltage | 240 V 5 A AC-12 || 30 V 2 A DC-13 || 240 V 1.5 A AC-15 | Reset Time | 25 ms on de-energisation |
Maximum Switching Voltage | 250 V AC/DC | Immunity To Voltage Dips | 30 % / 10 ms EN/IEC 61000-4-11 || 60 % / 100 ms EN/IEC 61000-4-11 || 95 % / 5 s EN/IEC 61000-4-11 |
Mechanical Durability | 30000000 cycles | Prot Against Electric Shocks | 4 kV class III IEC 60664-1 || 4 kV class III IEC 61812-1 |
Product Front Plate Size | 48 x 48 mm | Maximum Switching Current | 5 A |
In Rated Current | 5 A | Pick Up Duration | 55 ms |
Resist Electrostatic Dischrg | 6 kV in contact EN/IEC 61000-4-2 level 3 || 8 kV in air EN/IEC 61000-4-2 level 3 | Resist To Electromagn Fields | 9.14 V/yd (10 V/m) 26 MHz to 1 GHz IEC 61000-4-3 level 3 |
Relative Humidity | 93 % without condensation conforming to IEC 60068-2-3 | Time Delay Type | B || Di || A || C |
Mounting Support | Base mounted: socket || Panel mounted: system supplied with the product | Markings | CE |
Disturbance Radiated/conducted | Class B 0.15...30 MHz EN 55022 (EN 55011 group 1) | Type | Electronic timing relay |
Certifications / Standards | GL || UL || CULus || CSA || C-Tick | Green Premium Status | Green Premium product |
Ip Degree Of Protection | IP40 IEC 60529 housing) || IP50 IEC 60529 front face) | Local Signalling | Output relay state 1 LED yellow) || Flashing: relay energised timing in progress LED indicator green |
Electrical Connection | Plug-in sub-base 11 | Eu Rohs Directive | Pro-active compliance (Product out of EU RoHS legal scope) |
Component Name | RE48A | Discrete Output Type | Relay |
Brand | Schneider Electric | Control Type | Selector switch front panel |
Housing Material | Self-extinguishing | Weee | The product must be disposed on European Union markets following specific waste collection and never |
Mercury Free | Yes | Range Of Product | Zelio Time |