Load center, QO, 1 phase, 2 spaces, 2 circuits, 30A fixed main lugs, NEMA1, surface cover, CSA

QO2L30SC
Image
Maximum Number Of Tandem Breakers0Number Of Phases1 phase
Max Short Circuit Current Rating10 kANominal Voltage120/240 V AC
Maximum Number Of Single Pole Circuits2Number Of Spaces2
Box Number2Depth2.95 in (75 mm)
Ambient Air Temperature For Operation23 °F (-5 °C) || 104 °F (40 °C)Wiring Configuration3-wire
Width3.70 in (94 mm)Current Rating30 A
Height6.57 in (167 mm)Wire SizeAWG 12...AWG 10 aluminium || AWG 14...AWG 10 copper
Surface FinishBaked enamel greyEu Rohs DirectiveCompliant
Certifications / StandardsCSA || UL listedLoad Center TypeFixed Mains (lugs)
Green Premium StatusGreen Premium productGround BarGrounding bar (ordered separately)
TypeLoadcentreElectrical ConnectionLugs
Tightening TorqueMain lugs: 35 lb.in, AWG 12...AWG10, aluminium/copperEnclosure RatingNEMA 1 indoor
Marketing Trade NameQOBrandSquare D
Cover TypeSurface coverBusbar MaterialTin plated aluminium: busbar
Housing MaterialWelded sheet steelToxic Heavy Metal FreeYes
Reach Free Of SvhcYesMercury FreeYes